Installation
SP40S Multi-Function Communications System
56
AC Field Wiring
(non-power limited)
LINE, GROUND
and NEUTRAL
Thread wire out
knockout on the
left side of the
enclosure.
Grounding
Terminal
Block
Figure 22 VAC Input Connection
4.9.2 Installing Batteries
NOTE:
Batteries are not supplied with the SP40S Multi-Function Facility Communication
System and must be purchased separately.
1.
Connect the supplied red battery wire to the (+) terminal and the supplied black
battery wire to the (–) terminal of TB10 (see
2.
Run jumpers along the bottom of the chassis in the battery compartment.
To Positive
(+) of battery
terminal
(Red)
To Negative
(-) of battery
terminal
(Black)
Figure 23 Battery Wire Connections