Test Daylight Sensor Operation
The daylight sensor response can be tested by placing the sensor into test mode. During test mode, the daylight fade rate is lowered to 10
seconds and the time delays for dim-to-off functionality is reduced. The faster response allows the sensor operation to be quickly verified on
site. If test mode is activated for a closed loop daylight sensor, it must be manually deactivated when the test is completed. Test mode will not
automatically shut off.
Note
: If the device allows dim-to-off, when the measured light level exceeds 150% of the calibrated light level for more than 30 seconds, the sensor will
turn lighting OFF. Lighting will be turned back ON when one of the two conditions occurs. Condition 1: The measured light level falls between 100% and
50% of the calibrated light level for more than 20 seconds. Condition 2: The measured light level falls below 50% of the calibrated light level for longer
than 5 seconds
To use test mode:
1: Bring the mobile device within range (within 60 feet) of any provisioned WaveLinx Lite device in the desired area.
2: Ensure that the mobile device Bluetooth is turned on, and then open the WaveLinx Lite Mobile Application.
3: In the site list, select a site.
4: In the area list, select the desired area and verify that there is a network connection.
5: In the zone list, select the desired zone.
6: In the list of devices, locate the daylight sensor device. If needed, use the identify icon ‘ ‘ to flash the loads until the correct one is
found, and then tap the device to open the device details.
7: Tap ‘Daylight Sensor’ at the top of the device details pages to open to the daylight sensor view.
8: Slide the switch next to ‘Test Mode’ to the ON position and proceed to test the sensor.
Select the area
If needed, use ‘identify’ to
locate the correct device
Tap device to open
the device details
Select a zone
Select the site
Verify network
connection
Connected
Not connected
Tap ‘Daylight
Sensor’
Slide ‘Test Mode’ switch to
activate or deactivate
Test mode ON
Test mode OFF
Remember to slide ‘Test Mode’ switch to the OFF position once the test is complete. Test mode does not