UD70
Issue code: 70nu2
Features
8-7
8.7 Parameter
Descriptions
_
Q0%
Final speed demand
Units
Encoder lines per second
Range
–
–
2
31
to 2
31
Default
-----
Reset
H = CAL
S = CAL
P = CAL
_
Q0% gives the speed reference output from the PID controller in units of
encoder lines per second. The value is reset to 0 on power up.
_
Q1%
Auxiliary encoder position
Units
Encoder lines
Range
–2
31
to 2
31
Default
-----
Reset
H = S/V
S = N/A
P = 0
_
Q1% shows the position of the auxiliary (or reference) encoder, relative to
the position at power up. The DPL program can change the value in this
parameter at any time.
_
Q2%
Slave target position reference
Units
Encoder lines
Range
–2
31
to 2
31
Default
-----
Reset
H = S/V
S = N/A
P = 0
_
Q2% is the target position for the slave, and is used as the input to the
profile generation block. When selected, the control loop will attempt to
make the feedback position (
_
Q8% or
_
Q1%) equal to
_
Q2%. The actual
speed profile is modified by the ramp rates (
_
Q12% and
_
Q13%), ramp type
(linear or S-ramp), and maximum speed (_Q14%).
When running in speed mode (
_
Q32%.3 = 1),
_
Q2% is updated with the
calculated stopping position.