UD70
Issue code: 70nu2
9-2
Diagnostics
9.2
Run-time trip codes
When the Drive is tripped, the display shows
tr
followed by a two-digit
number (eg.
tr 41
). The error number can be determined in an
ERROR
task
by reading virtual parameter #88.01.
The possible trip codes are as follows:
Error
number
Description
Action
40
Unknown error
Always trips
41
Parameter does not exist
Trips when #17.14 = 1
42
Parameter write failed: parameter is read only
Trips when #17.14 = 1
43
Parameter read failed: parameter is write only
Trips when #17.14 = 1
44
Parameter write failed: parameter value is over-range
Trips when #17.14 = 1
and #17.17 = 1
45
Virtual parameter access failed:
IOLINK
is not running
Trips when #17.14 = 1
and #17.15 = 1
46 ~ 48
Internal error
Always trips
49
Wrong system loaded
Always trips
50
Maths error in the program, eg. divide by zero, overflow, etc
Trips when #17.14 = 1
51
DPL array index is out of range
Trips when #17.14 = 1
52
User generated trip from control word
Always trips
53
DPL program incompatible
Always trips
54
DPL overload – a task has run out of time
Trips when #17.14 = 1
55
RS485 trip (mode 3, mode 4, etc)
Trips when #17.14 = 1
and #17.15 = 1*
56
Option module and system-file are incompatible
Always trips
57
Illegal operating system call
Always trips
58 - 59
Internal error
Trips when #17.14 = 1
60 - 69
High speed communications option generated trips
Trips when #17.14 = 1
Prc2
Watchdog trip (see WDOG command, chapter 7)
Trips when #17.18 = 1
(* Trip 55 occurs only when an I/O Box is connected and operating, and
Mode 3 or 4 serial communications fail.)