UD70
Issue code: 70nu2
Installation
2-3
Downloading the system file
The
UD70
has no pre-loaded system software. The first task is to program
the system software using the DPL Toolkit. Use the following procedure:
1
Connect the serial communications cable to the
UD70
.
2
Apply
AC
power to the Drive.
3
In Windows 3.xx Program Manager, or in the Windows 95 Start menu,
click on:
The
DPL
DPL Toolkit
Toolkit window appears. At the top of the window are a
menu bar and toolbar.
4
If the serial port of the host
PC
is not
COM1
, open the Projects
Projects menu
and select Configure
Configure. In the drop-down menu that appears, select
Comport
Comport. This opens a further drop-down menu which allows
selection of the required communications port.
5
Click on
(Open Task Manager
Open Task Manager). After a few moments, the DPL
DPL
Task Manager
Task Manager dialog box appears.
If the dialog box does not appear, and all the buttons in the lower
toolbar of the window appear shaded (inactive), communications
could not be established with the
UD70
. Check the connecting cable is
correct, and the correct
COM
port is used.
6
Click on
. The File Viewer
File Viewer dialog box appears.