UD70
Issue code: 70nu2
Serial communications
6-9
Re-reading data
Once a read message has been received and understood (ie. valid data was
returned), to request the parameter again, request the next parameter, or
the previous parameter, a single control code character may be sent. These
control codes are:
Control
Code
Function
Keyed as...
NAK
Return the value of the same parameter
Ctrl U
ACK
Read the next parameter
Ctrl F
BS
Read the previous parameter
Ctrl H
This facility can be used to save time when monitoring a parameter over a
period of time.
Writing to parameters
To write data to a parameter (Drive or virtual), the message structure is
comprised as follows:
Control
Address
Control
Parameter
Data
Control
BCC
EOT
GA GA UA UA
STX
M1 M2 P1 P2 D1 ... Dn
ETX
Where:
GA
= Group
address
GU
= Unit
address
M1 M2
= Menu
number
P1 P2
= Parameter
number
D1...DN
= Data
First character:
+ or Space for positive values
–
– for negative values
X
X for hex. values
BCC
= Block
checksum
The data field can be of a variable length with the maximum length being
dependent on the parameter being edited.