UD70
Issue code: 70nu2
Reference
7-21
WDOG
Syntax
WDOG
The
WDOG
instruction is used to update the DPL program watchdog.
The watchdog facility is enabled by setting the appropriate set-up
parameter at 1, and issuing a
WDOG
instruction. When enabled, the
WDOG
instruction must be executed within every 200ms. If a
WDOG
instruction is
not executed within 200ms, the Drive trips on Prc2 trip
Prc2 trip.
The
WDOG
instruction can be used only in the
INITIAL
and
BACKGROUND
Tasks. The
UD70
operating system automatically updates the individual
watchdogs of the real-time tasks.
See the on-line Help for an example.
Notes
If any of these tasks are single-stepped a watchdog trip
will occur.
When a watchdog trip occurs, the Drive trips on Prc2.
Because the watchdog trip is a function of the Drive, the
DPL program continues to run.
This function is not available on the Vector Drive.