Software Travel Limits
Software Travel limits can be used to limit machine travel. They are often setup inside the
hardware travel limits to add another level of security or protection from exceeding the
machines travel limits. The FM-3 module constantly monitors the feedback position, and if
this position exceeds the values entered for Software Travel Limit + or -, then the drive will
decel to a stop. Software Travel Limits are not functional unless the AbsolutePosnValid
source is active. AbsolutePosnValid is active upon successful completion of a home or the
DefineHome destination is activated.
To recover from a software travel limit, a jog may be commanded in the opposite direction of
travel. For example, if a software travel limit - is hit, then the axis can be jogged in the +
direction.
Software Travel Limit +
If the absolute position is greater than or equal to this value the Software Travel Limit Plus
Active source shall activate.
A rising edge occurs when the absolute position is greater than or equal to the parameter
Software Travel Limit +. A falling edge will be generated as soon as the above is not true.
Software Travel Limit -
If the absolute position is less than or equal to this value the Software Travel Limit Minus
Activate shall activate.
A rising edge occurs when the absolute position is less than or equal to the parameter
Software Travel Limit -. A falling edge will be generated as soon as the above is not true.
Rotary Group
Rotary Rollover Check Box
Check this box to enable (or disable if not checked) the rotary rollover feature.
Rotary Rollover
This parameter is used in rotary applications and determines the position at which the internal
position counter will be reset to zero.
Example:
The user has a rotary table application with distance user units of degrees, 360.00 degrees/1
rev. The Rotary Rollover would be set to a value of 360°.
The motor is traveling in the positive direction. As the feedback position reaches 359.999 and
continues on, the feedback position will reset (or roll-over) to zero. If the motor changes
direction and travels in the negative direction, the position will rollover at 0 to 359.999
degrees and count down. The resolution of the rotary rollover point is determined by the
Summary of Contents for FM-3
Page 2: ......
Page 14: ...xii ...
Page 16: ...2 FM 3 Programming Module Reference Manual Figure 2 FM 3 Programming Module Features ...
Page 128: ...114 FM 3 Programming Module Reference Manual ...
Page 156: ...142 FM 3 Programming Module Reference Manual ...
Page 196: ...182 FM 3 Programming Module Reference Manual ...
Page 238: ...224 FM 3 Programming Module Reference Manual ...
Page 251: ...237 Diagnostics and Troubleshooting Figure 97 Diagnostic Cable DGNE Diagram ...
Page 262: ...248 FM 3 Programming Module Reference Manual ...
Page 264: ...250 FM 3 Programming Module Reference Manual AX4 CEN CDRO ...
Page 265: ...251 Specifications Cable Diagrams ...
Page 266: ...252 FM 3 Programming Module Reference Manual SNCE XXX Cable SNCDD 001 5 Cable ...
Page 267: ...253 Specifications SNCO 003 Cable SNCI 003 Cable ...
Page 268: ...254 FM 3 Programming Module Reference Manual SNCLI 003 Cable ...
Page 272: ...258 FM 3 Programming Module Reference Manual TIA XXX Cable DDS XXX Cable ...
Page 274: ...260 FM 3 Programming Module Reference Manual CMDS XXX Cable CMMS XXX Cable ...
Page 275: ...261 Specifications CFCS XXX Cable ...
Page 276: ...262 FM 3 Programming Module Reference Manual CFCO XXX Cable ...
Page 277: ...263 Specifications CFOS XXX Cable ...
Page 278: ...264 FM 3 Programming Module Reference Manual ...
Page 286: ...272 FM 3 Programming Module Reference Manual ...
Page 290: ...276 FM 3 Programming Module Reference Manual ...
Page 291: ......