come to a halt, but the index's velocity command remains at the velocity it was at before the
feedhold was activated. When the feedhold is deactivated time will ramp back up and the
index will continue on to its programmed distance or position. Feedhold affects indexes,
homes, and programs. A jog is not affected by the feedhold unless it is initiated from a
program. This is level sensitive.
Feedhold Deceleration Time
FeedholdDecelTime
When Feedhold destination is activated the motor will decelerate to a stop in the time
specified by the FeedholdDecelTime parameter. While the feedhold destination is active, the
motion profile is stopped.
FeedRate Deactivate
FeedRateDeactivate
This destination allows the user to deactivate the FeedRate Override feature. When FeedRate
Deactivate is enabled, FeedRate Override will be disabled and all index or home motion will
operate at its programmed velocity. When FeedRate Deactivate is disabled, FeedRate
Override will be enabled, and index and home motion is subject to scaling by the FeedRate
Override parameter. The default value for FeedRate Override is 100%, so even when
FeedRate Override is enabled, default motion will run at programmed velocity.
FeedRate Override
FeedRateOverride
This parameter is used to scale all motion. It can be described as “scaling in real time.” The
default setting of 100% will allow all motion to occur in real time. A setting of 50% will scale
time so that all motion runs half as fast as it runs in real time. A setting of 200% will scale
time so that all motion runs twice as fast as it would in real time. FeedRate Override is always
active, and this parameter may be modified via Modbus or in a program. When changed, the
new value takes effect immediately.
Foldback Active
FoldbackActive
This source (output function) is active when the drive is limiting motor current. If the
Foldback RMS exceeds 100 percent of the continuous rating, the current foldback circuit will
limit the current delivered to the motor to 80 percent of the continuous rating.
Summary of Contents for FM-3
Page 2: ......
Page 14: ...xii ...
Page 16: ...2 FM 3 Programming Module Reference Manual Figure 2 FM 3 Programming Module Features ...
Page 128: ...114 FM 3 Programming Module Reference Manual ...
Page 156: ...142 FM 3 Programming Module Reference Manual ...
Page 196: ...182 FM 3 Programming Module Reference Manual ...
Page 238: ...224 FM 3 Programming Module Reference Manual ...
Page 251: ...237 Diagnostics and Troubleshooting Figure 97 Diagnostic Cable DGNE Diagram ...
Page 262: ...248 FM 3 Programming Module Reference Manual ...
Page 264: ...250 FM 3 Programming Module Reference Manual AX4 CEN CDRO ...
Page 265: ...251 Specifications Cable Diagrams ...
Page 266: ...252 FM 3 Programming Module Reference Manual SNCE XXX Cable SNCDD 001 5 Cable ...
Page 267: ...253 Specifications SNCO 003 Cable SNCI 003 Cable ...
Page 268: ...254 FM 3 Programming Module Reference Manual SNCLI 003 Cable ...
Page 272: ...258 FM 3 Programming Module Reference Manual TIA XXX Cable DDS XXX Cable ...
Page 274: ...260 FM 3 Programming Module Reference Manual CMDS XXX Cable CMMS XXX Cable ...
Page 275: ...261 Specifications CFCS XXX Cable ...
Page 276: ...262 FM 3 Programming Module Reference Manual CFCO XXX Cable ...
Page 277: ...263 Specifications CFOS XXX Cable ...
Page 278: ...264 FM 3 Programming Module Reference Manual ...
Page 286: ...272 FM 3 Programming Module Reference Manual ...
Page 290: ...276 FM 3 Programming Module Reference Manual ...
Page 291: ......