Status
Power Mode LED
Run LED
Status LED (shows functional status)
Forced I/O LED
Digital Inputs / Outputs
8 LEDs
Counters
3 LEDs
LAN
Link indicator (LINK) LED
Activity indicator (ACT.) LED
Push-button
LED power toggle
16.6 Power
Supply
DC power Input
30V maximum
10.0 to 11.5V turn on
9.5V typical turn off
12mW at 12V during Sleep
510mW at 12V during normal operation. 32MHz., LEDs off, no
expansion, LAN and USB disabled.
320mW at 12V during reduced power mode operation. 12MHz.,
LEDs off, no expansion, LAN and USB disabled. (Reduced power
mode)
1.2W at 12V during normal operation. 32MHz., LEDs off, no
expansion, LAN enabled and USB disabled.
Add 25 to 100mW when enabling the LEDs.
12W at 24V maximum. 5V supply fully loaded and Vloop on and
boosted, fully loaded.
Output capacity
5V at 1.2A capacity
5V at 80mA required by 5209 controller (LAN and USB disabled)
5V at 40mA required by 5209 controller (LAN and USB disabled)
in reduced power mode.
5V at 160mA required by 5209 controller to enable the LAN
5V at 50mA required by 5209 controller to enable the USB
5V at 1.1A (current limited) for COM2 and I/O expansion
5V at 250mA (current limited) on COM3 for Vision displays
5V at 100mA (current limited) for USB downstream port loads
Vloop: 24V at 0.14A available for the 5 analog inputs and 2
optional analog outputs
Efficiency
85%, 12Vdc input, full load
16.7 I/O
Capacity
5000 Series I/O
Expansion
Capacity
Maximum 40 I/O modules.
Refer to the System Configuration Guide for further details.
SCADAPack 350 Hardware Manual
February 14, 2007
59