FACTORY BOOT mode is selected by performing the following procedure:
1.
Remove power from the SCADAPack controller.
2.
Hold down the LED POWER button.
3.
Apply power to the SCADAPack controller.
4.
Continue holding the LED POWER button for longer than 30 seconds until the STAT LED
turns solid.
5.
Release the LED POWER button.
The FACTORY boot will take approximately 60 seconds to complete. During this time the
controller may appear unresponsive while the file system is being formatted to fix any corruption.
The STAT LED will remain on until the FACTORY boot has completed.
13.1.5
Boot Mode Effects
The table below summarizes the effects of the various boot modes.
Run
Boot
Service
Boot
Cold
Boot
Re-entry
Boot
Factory
Boot
Action
X
X
X
IP Address set to default
X
X
X
X
serial settings set to
default
X
X
X
Lock settings set to
default
X
X
X
S&F settings set to
default
X
X
X
FIP set to default
X
X
X
LED power set to default
X
X X
Register
assignment
erased
X
X X
Database
initialized
X
X
X
logic app(s) erased
X
X
C Applications Erased
X
X
All files are erased
X
Flash File System
reformatted
X C
Applications
started
X logic
application
started
X Communication
settings
on active interface
retained
X
X
X
Settings saved to non-
volatile memory
X
X
ladder logic in flash is
erased
X
X
X
X
All protocols are set to
defaults