How To Use Collection Data
—
M2M Gateway PLC Communication Settings
—
95
—
2.
OPC UA Server function
The CONPROSYS has an OPC UA server function, and the digital/analog interface information or the
information obtained with PLC communication can be acquired from remote devices.
Note that information obtained with PLC communication can be acquired up to 1,000 pieces from
remote device.
Function Specification
Item
Specification
Endpoint URL, Server URL
opc.tcp://[IP Address]
Access type
Data Access (Synchronization I/O)
Profile
Embedded UA Server Profile
Communication protocol
UA TCP Binary
Security policy
None, Basic128Rsa15, Basic256, Basic256Sha256
Security mode
Anonymous, Username/Password, Certificate/Private Key
Node tree structure
Node editing
Not Available (Fixed)
Address Space Specification
OPC UA Node
Sub Folder
Node Name
Data
Type
Access
Data Range
Digital Input
Bit0, Bit1, Bit2, Bit3
Digital_Input DI00, DI01, DI02, DI03 Boolean Read
0, 1
Digital Output
Bit0, Bit1
Digital_Output DO00, DO01
Boolean Read/Write 0, 1
Analog Input
Channel0, Channel1
Analog_Input AI00, AI01
UInt32
Read
0 - 4095
Counter Input
Channel0, Channel1
Counter
CNT00, CNT01
UInt32
Read
0 - 16777215
Counter Input Clear
Channel0, Channel1
Counter_Clear
CNT00_CLR,
CNT01_CLR
Boolean Read/Write 0, 1
Serial communication
*1
Letter output
Product name
The total number of
processed parts
Value data in any type
1 - 10
String data in any type
1-10
COM
PrintOutput
ProductName
ProductResultNumber
value01 - value10
string01 - string10
String
String
Int32
Double
String
Read
Rely on a
DPRNT content
prescribed in
the CNC
program