PLC Communication Settings
—
M2M Gateway PLC Communication Settings
—
61
—
Device Configuration
The device configuration details are listed below.
Device configuration 1
Device configuration 2
*Notice
- Set a Modbus address respectively when configuring more than one device setting.
The setting example is as follows;
Device configuration 1 : 0 – 9 (2000h - 2009h), Device configuration 2 : 10 – 19 (200Ah - 2013h)
- “Data Type”, “Cloud Key”, and “Cloud Interval” are the functions to file-record and send
the periodically read information in units of device settings. It is omitted in this particular example.
For more details on the setting, check the "3.Data Transfer to a Higher Level" in the next chapter
"How to use Collection Data".
Be careful they should be specified in decimal notation.
An example) Start / End addresses : Specify 1000 -1009
Slave address to actually access : 03E9h~03F2h
In addition to the conversion from decimal to hexadecimal,
the address is incremented by 1.
This is due to the Modbus protocol regulations.