Error messages 179
Location:
Interconnect module - side A (10-connector)
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
1.
Press the server blade management module reset button.
2.
Reseat the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP website
(
http://www.hp.com/products/servers/proliant-bl/p-class/info
).
3.
Replace the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP website
(
http://www.hp.com/products/servers/proliant-bl/p-class/info
).
Interconnect Module A (6-Connector) Error Code
LED code:
17-1 or 17-2
Location:
Interconnect module - side A (6-connector)
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
1.
Press the server blade management module reset button.
2.
Reseat the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP website
(
http://www.hp.com/products/servers/proliant-bl/p-class/info
).
3.
Replace the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP website
(
http://www.hp.com/products/servers/proliant-bl/p-class/info
).
Interconnect Module B (10-Connector) Error Code
LED code:
16-1 or 16-2
Location:
Interconnect module - side B (10-connector)
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
1.
Press the server blade management module reset button.
2.
Reseat the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP website
(
http://www.hp.com/products/servers/proliant-bl/p-class/info
).
3.
Replace the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP website
(
http://www.hp.com/products/servers/proliant-bl/p-class/info
).
Interconnect Module B (6-Connector) Error Code
LED code:
18-1 or 18-2
Location:
Interconnect module - side B (6-connector)
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
1.
Press the server blade management module reset button.
2.
Reseat the interconnect module.