IE-LGR-Uxxxx-16
Contact resistance for the "switched-off" state:
> 2 MΩ
Excitation voltage: approx. 3 V
Minimum state duration necessary for latching the
state: 1s
Connection:
Pluggable terminal block, maximum wire cross section
1.5 mm
2
. The maximum cable length is 30 m. It is
recommended to use shielded cables.
CAUTION: The inputs are not galvanically isolated!
Recommended calibration interval:
2 years
U7844
_________________________________________
Measured values:
2x user configurable binary input for voltage or dry
contact (as e.g. an open-collector transistor). This input
is able to catch also the „voltage applied/not applied“
states.
2 x counting input. This input, like the binary one, can be
configured to voltage or dry contact (as e.g. an open-
collector transistor). These counting inputs can be used
as additional two binary ones.
Input levels:
Binary or counter input configured for voltage
measurements:
Input voltage for the „L“ level: < 0.8 V
(*)
Input
voltage for the „H“ level: > 2 V
Minimum applicable voltage: 0 V
Maximum applicable voltage: +30 V DC
(*)
When the input is disconnected, the device will
measure the „L“ level.
Binary or counter input configured for a dry contact or
an open-collector transistor:
Contact resistance for the „switched-on“ state:
< 10 kΩ
Contact resistance for the "switched-off" state:
> 2 M
Ω
Excitation voltage: approx. 3 V
Minimum state duration necessary for latching
the state: 1s
Counter parameters:
Range: 24 bits (16 777 215), possibility of letting the
counter overflow
Summary of Contents for U0110
Page 5: ...IE LGR Uxxxx 16 5 General view of a Uxxxx series datalogger U0141 model...
Page 64: ...64 IE LGR Uxxxx 16 Dimensions U0110 U0111 U0122...
Page 65: ...IE LGR Uxxxx 16 65 U0121 U0141...
Page 66: ...66 IE LGR Uxxxx 16 U0246 U0141T U0541 U5841 U6841 U7844 U2422...
Page 67: ...IE LGR Uxxxx 16 67 U3121 U3120 U4130...
Page 68: ...68 IE LGR Uxxxx 16 U3430 U4440 U3631...
Page 69: ...IE LGR Uxxxx 16 69 U8410...