InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
1-3
Introduction
Congratulations to your purchase of ComAp InteliPro protection relay unit! InteliPro is a
microprocessor-based door-mounted protective device, providing a comprehensive set of protective
and supplementary functionalities. ComAp unique modular concept of HW extension modules, SW
options and full configurability allow perfect solution for most of the generator-to-mains parallel
applications.
For the complete list of protective functions please refer to the chapter
Protective functions in detail
. The full
feature allows to cover advanced requirements for mains-
decoupling (inter-
tie, „G59/
3
“), as well as
other advanced protection applications.
Conformity declaration
Following described machine complies with the appropriate basic safety and health
requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type,
as brought into circulation by us.
VDE O126-1-
1
The unit is certified to comply to the appropriate requirements of the
standard DIN V VDE V 0126-1-1 (certificate ref. 44 207 11 398020,
available upon request), with the following conditions:
The conformity with the Standard DIN V VDE V 0126-1-1,
chapter 4.1/ 6.1, which is declared in the certificate 44 207 11
398020, requires the tolerance against one fault. In order to fulfil
this functional safety requirement, a redundant architecture has
to be built by the usage of two certified units.
It has to be ensured that each of both units is connected to an
output (relay) which is capable to induce opening of the
operated contactor.
Warnings
Be aware that the relay outputs can change state during and after the unit
setting (before the unit is used again ensure that the proper setting is done)!!!
Be aware that the devices connected to binary outputs of the unit may operate
upon disconnection of power supply, measurement inputs and/or binary
inputs!!!
!!! CAUTION !!!
Dangerous voltage
In no case touch the terminals of voltage measurement!
Adjust set points
All setpoints are pre-adjusted to their typical values. Before putting into operation, the setpoints must
be checked and/or adjusted to the required values.