InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-12
f< Prot
Separate output for underfrequency protection. Active if the underfrequency protection is active or not
acknowledged by Fault Reset.
f> Prot
Separate output for overfrequency protection. Active if the overfrequency protection is active or not
acknowledged by Fault Reset.
V Unb Prot
Separate output for voltage unbalance protection.
Dyn Volt Prot
Separate output for dynamic grid support protection.
CtrlHBeat FD
Output for signalization of the Heartbeat feedback. The output is activated in case there is no
Heartbeat signal from an appropriate controller coming to the binary input
QU Gen Prot
Separate output for the “QU” protection to open the GCB.
QU Mns Prot
Separate output for the “QU” protection to open the MCB.
PhaseRot Prot
Separate output for phase sequence protection.
VectorS Prot
Separate output for vector shift protection.
ROCOF Prot
Separate output for ROCOF protection.
DOC Prot
Separate output for directional overcurrent protection.
P Prot
Separate output for mains reverse power protection.
I> Prot
Separate output for overcurrent (ANSI 50 and 51) protection.
NVD Prot
Separate output for neutral voltage displacement protection.
!NVD Prot
Separate output for inverted signal of Neutral Voltage Displacement protection.
EFC Prot
Separate output for earth fault current (ANSI 50N and 51N) protection.