InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-19
Default setting: 0 s
CB2 Prot Timer [s]
Setting of the CB2 Protection timer. For this time after CB2 Feedback de-energization, the output CB2
Protection keeps in de-energized state to prevent premature breaker closing. After this time it goes
back to energized state.
Step:
1 s
Range:
1 - 60 s
0 = OFF, CB2 protection function is disabled
Default setting: 0 s
Comms Settings
Contr. Addr
Unit identification address number. In case of connection to CAN bus together with other ComAp
controllers, different address than that of the controllers has to be entered.
Range:
1 - 32
Default: 1
COM1 Mode
[DIRECT / MODEM / MODBUS]
Switch, defining what protocol/mode of communication is used on the plug-in communication module.
DIRECT:
InteliPro (LiteEdit) communication protocol
MODEM:
Analog or GSM modem
MODBUS :
InteliPro Modbus protocol
Default setting: DIRECT
N
OTE
:
For a module, providing 2 communication channels, this switch defines the communication on the first
channel (RS232 in case of IL-NT RS232-485).
COM2 Mode
[DIRECT / MODEM / MODBUS]
Switch, defining what protocol/mode of communication is used on the second communication channel
of a plug-in communication module.
DIRECT:
InteliPro (LiteEdit) communication protocol
MODEM:
Analog or GSM modem
MODBUS :
InteliPro Modbus protocol
Default setting: DIRECT
N
OTE
:
For a module, providing 2 communication channels, this switch defines the communication on the
second channel (RS485 in case of IL-NT RS232-485).
ModemIniString
Auxiliary modem initialization string
–
executed after the default modem initialization string in case of
modem communication.
ModbusComSpeed
[9600 / 19200 / 38400 / 57600 bps]
Adjusting of the speed of Modbus communication
Default setting: 9600 bps
CAN Bus Mode [32C / 8C]
CAN bus speed selection. Use this setpoint in case that you operate InteliPro together with other
ComAp contollers connected via CAN bus.
32C:
High speed CAN (250 kbps) applicable up to 32 controllers, CAN bus length limited up
to 200 meters.