InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-39
Date/Time
TimeStamp Per [min]
Time interval for history record. Time base is based on number of minutes since midnight. History
records are only made in parallel, if CB1 Feedback and CB2 Feedback are configured and closed,
activation delay elapsed and if there is at least one unblocked protection. If CB1 Feedback and CB2
Feedback are not configured, history records are made in case that there is at least one unblocked
protection.
Step:
1 min
Range:
0 - 240 min
0 = OFF, TimeStamp event is disabled
Default setting: 30 min
#SummerTimeMod
[DISABLED / WINTER / SUMMER, WINTER-S,
SUMMER-S]
DISABLED:
Automatic switching between summer and wintertime is disabled.
WINTER (SUMMER):
Automatic switching between summer and wintertime is enabled and it is
set to winter (summer) season.
WINTER-S (SUMMER-S): Modification for southern hemisphere.
Default setting: DISABLED
N
OTE
:
In case of interconnection of InteliPro with other ComAp units on the CAN2 bus, the setpoint is
automatically synchronized within the interconnected group.
#Time
[HHMMSS]
Real time clock adjustment.
N
OTE
:
In case of interconnection of InteliPro with other ComAp units on the CAN2 bus, the setpoint is
automatically synchronized within the interconnected group.
#Date
[DDMMYY]
Actual date adjustment
N
OTE
:
In case of interconnection of InteliPro with other ComAp units on the CAN2 bus, the setpoint is
automatically synchronized within the interconnected group.
Sensors Spec
AI1Calibration, AI2Calibration, AI3Calibration, IOM AI1 Calibr, IOM AI2
Calibr, IOM AI3 Calibr, IOM AI4 Calibr
The value for calibration of the appropriate analog input of the unit or extension module IG-IOM or
IGS-PTM. This value is added to the output of analog input curve.