![ComAp InteliPro Installation And Operation Manual Download Page 94](http://html.mh-extra.com/html/comap/intelipro/intelipro_installation-and-operation-manual_2638971094.webp)
InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-38
CU AI1 BlockBI, CU AI2 BlockBI, CU AI3 BlockBI
[Block 1 / Block 2 /
Block 1+2 / None]
Selection of blocking binary input for protections assigned to analog input 1, 2 or 3 of the unit
respectively.
Default setting: None
IOM Analog In
Setpoints in this group are used for protection on DC analog inputs of the extension module IG-IOM or
IGS-PTM.
IOM AI1 Wrn, IOM AI2 Wrn, IOM AI3 Wrn, IOM AI4 Wrn
Level of warning type of protection assigned to analog input 1, 2, 3 or 4 of the extension module IG-
IOM or IGS-PTM. The step, decimals, range and units are given by configuration of the appropriate
output.
IOM AI1 Trp, IOM AI2 Trp, IOM AI3 Trp, IOM AI4 Trp
Level of trip assigned to analog input 1, 2, 3 or 4 of the extension module IG-IOM or IGS-PTM
respectively. The step, decimals, range and units are given by configuration of the appropriate output.
IOM AI1 Del, IOM AI2 Del, IOM AI3 Del, IOM AI4 Del [s]
Delay of protections assigned to analog input 1, 2, 3 or 4 of the extension module IG-IOM or IGS-PTM
respectively. It is the same for warning alarm and trip.
Step:
1 s
Range:
0 - 600 s
Default setting: 5 s
IOM AI1 BlockBI, IOM AI2 BlockBI, IOM AI3 BlockBI, IOM AI4 BlockBI
[Block 1 / Block 2 / Block 1+2 / None]
Selection of blocking binary input for protections assigned to analog input 1, 2, 3 or 4 of the extension
module IG-IOM or IGS-PTM respectively.
Default setting: None
SMS/E-Mail
Wrn Alarm Msg [OFF/ ON]
Enables or disables active calls, SMS or e-mail mesages to the selected phone, mobile or e-mail
address when a warning alarm occurs.
Default setting: OFF
Trp Alarm Msg [OFF/ ON]
Enables or disables active calls, SMS or e-mail mesages to the selected phone, mobile or e-mail
address when trip occurs.
Default setting: OFF
TelNo/Addr Ch1, TelNo/Addr Ch2
2 possibilities of enetring phone number or e-mail to which the message will be sent in case that
warning or trip occurs.