Environmental conditions
• The air temperature in the fan coil intake area (in
the middle of the grill intake area) must be between
6 and 40°C. The temperature must never exceed
these limits.
• Relative humidity must be between 15 and 75%.
Air-conditioning
Both the
a-CXW 0402-0502-0602-0702 / 0404-0504-0604-
0704
i-CXW 0502-0602-0702 / 0504-0604-0704
modules and the
a-CXW 0802-1102-1202 / 0804-1104-1204
i-CXW 0802-1102 / 0804-1104
modules are fitted with three primary air intakes at the
corners of the units.
This air is mixed with the air taken in from the room
inside the appliance.
The air-conditioning intake pressure is slightly
lower than atmospheric pressure.
This low pressure should not be considered in the
design of the air-conditioning system.
To connect the appliance’s air pipes, a Ø 110 pipe
adapter to be fitted on the primary air intakes is availa-
ble as an accessory (supplied separately).
The flow of conditioned air is limited to 20% of the
total fan coil air flow at medium speed, with a maxi-
mum of 100 m³/h for each opening.
INSTALLATION
a-CXW 0402-0502-0602-0702 / 0404-0504-0604-0704
i-CXW 0502-0602-0702 / 0504-0604-0704
a-CXW 0802-1102-1202 / 0804-1104-1204
i-CXW 0802-1102 / SK 0804-1104