Regeneration and Error Screens

Regen Screen

Displays the time remaining in the current cycle. Pressing REGEN advances to the next cycle.

Error Screen

Alternated 

fl

 ashing Err and error code every 3 seconds. Clear by disconnecting 

the power supply at the PC board and reconnecting, or press NEXT and 
REGEN simultaneously for 3 seconds.

In Alternator Systems when a unit is waiting to initiate the 

fi

 rst cycle step of regeneration, 

“REGEN Pndg” is displayed.

“REGEN Pndg RINSE FILL” is displayed whenever a zero-capacity tank has transferred to 
an off-line state and is currently waiting to initiate the second portion of a regeneration cycle. 
Viewed only when Delayed Rinse and Fill is set to ON.

“STbY” is displayed in Alternator Systems when a valve is in Standby state.

The user can initiate manual regeneration. The user has the option to request the manual regeneration at the delayed regeneration 
time or to have the regeneration occur immediately:
1. Pressing and releasing the REGEN button. REGEN TODAY will 

fl

 ash on the display and the regeneration will occur at the 

delayed regeneration time. The user can cancel the request by pressing and releasing the REGEN button.

2. Pressing and holding the REGEN button for approximately 3 seconds will immediately start the regeneration. The user cannot 

cancel this request, except by resetting the control by pressing NEXT and REGEN simultaneously for 3 seconds.

Regeneration Cycles and Times

Button Operation and Function

Changes variable being displayed.

Pressing once and releasing will schedule a regeneration at the preset delayed regeneration time. 
Pressing again and releasing will cancel the regeneration.
Pressing and holding for 3 seconds will initiate an immediate regeneration
Pressing while in regeneration will advance to the next cycle.
Pressing in the program levels will go backwards to the previous screen

Key sequence to lock and unlock program settings.

Scrolls to the next display.

Holding for 3 seconds initiates a control reset. The software version is displayed and the piston returns
to the home/service position, resynchronizing the valve.

Used with valve type 1.0  , holding for at least 3 seconds causes a switch in the tank in Service without cycling 
the regeneration valve. After tank switch, days remaining and capacity remaining status is retained for each 
tank until the next regeneration.

Range

Cycle

Softening

Filtering Regen

Filtering 
Backwash

Backwash
Regenerant Draw/Slow Rinse (UP or DN)
Fast Rinse
Regenerant Re

fi

 ll

Regenerant Re

fi

 ll 2.0 or 1.5 set to MIN (softening only)

Service

1-120 minutes
1-180 minutes
1-120 minutes
0.05-90.0 Kg
0.1-99.0 minutes
1-480 minutes

1-120 minutes
1-180 minutes
1-120 minutes
0.2-76.0 Liters
0.1-99.0 minutes
NA

1-120 min.
NA
1-120 min.
NA
NA
NA

All cycles can be set to “oFF”.

Summary of Contents for Water Specialist EI

Page 1: ...Water Specialist EI Control Valve Programming and Cover Drawing Manual...

Page 2: ...Page 2 EI Manual...

Page 3: ...EI Front Cover and Drive Assembly 4 Regeneration and Error Screens 5 User Displays 6 Configuration Settings 7 OEM Softener System Setup 11 Setting Options Table 14 OEM Filter System Setup 15 Installer...

Page 4: ...ront Cover and Drive Assembly AC Adapter U S International Supply Voltage 120V AC 230V AC Supply Frequency 60 Hz 50 Hz Output Voltage 15VDC 15VDC Output Current 500 mA 500 mA 1 Battery replacement is...

Page 5: ...user cannot cancel this request except by resetting the control by pressing NEXT and REGEN simultaneously for 3 seconds Regeneration Cycles and Times Button Operation and Function Changes variable bei...

Page 6: ...turn to the User Displays Time of day should only need to be set after power outages lasting more than 8 hours if the battery has been depleted and a power outage occurs or when daylight saving time b...

Page 7: ...ignal or one dP switch cannot be used for both controls on0 If the dP switch is closed for an accumulative time of 2 minutes a regeneration will be signaled to the unit In a twin alternating system th...

Page 8: ...peration For separate source operation the three wire communication cable is not used Selection requires that a connection to a Clack Motorized Alternator Valve MAV is made to the two pin connector la...

Page 9: ...rvice Position MAV piston rod Extended WS1 WS1 25 and WS1 5 Valves For Clack Corporation alternator systems using WS1 WS1 25 and WS1 5 valves there will be an option to delay the last two cycles of re...

Page 10: ...o Hard Water Bypass V3097 BSPT or V3098 BSPT to the two pin connector labeled MAV located on the printed circuit board is required Press NEXT to go to Step 6CS Press REGEN to return to previous step S...

Page 11: ...he brine tank after the final rinse or PrE to refill the brine tank four hours before the regeneration time set This screen is not viewed when Step 2S is set to Filtering Press NEXT to go to Step 5S P...

Page 12: ...matically calculated and reserve capacity will be automatically estimated oFF regeneration will be triggered solely by the day override setting see Installer Display Settings Step 4I a volume regenera...

Page 13: ...e meter Ranges from 1 to 200 liters Press NEXT to go to Step 15S Press REGEN to return to previous step Step 15S Set Relay Deactivate Time using or If Set Time on is selected in Step 13S the relay wil...

Page 14: ...be allowed to be set because regeneration will always occur when volume capacity reaches 0 Any number on 0 oFF Reserve capacity NOT automatically estimated Regeneration occurs immediately when volume...

Page 15: ...M3 See Setting Options Table for more detail Press NEXT to go to Step 6F Press REGEN to return to previous step Step 5F Step 6F Set Regeneration Time Options using or If value is set to NORMAL means r...

Page 16: ...from 1 second to 20 minutes Press NEXT to exit OEM Filter System Setup Press REGEN to return to previous step Step 9F EXIT OEM FILTER SYSTEM SETUP Step 7F Set Relay Operation using or The choices are...

Page 17: ...ximum number of days between regenerations If value set to oFF regeneration initiation is triggered solely by volume used If value is set in days allowable range from 1 to 28 regeneration initiation w...

Page 18: ...shows the total number of regenerations that have occurred since startup Press the NEXT button to go to Step 6D Press REGEN to return to previous step Step 5D Step 6D Error Log This display shows a hi...

Page 19: ...f A then the tank with the valve on it was in service if b the tank with the in out head on it was in service The next three digits represent the number of hours ago that the transfer occurred The dis...

Page 20: ...Page 20 EI Manual...

Page 21: ...EI Manual Page 21...

Page 22: ...Page 22 EI Manual...

Page 23: ...History 3 12 2015 PAGE 12 Step 13S Clarified relay operation PAGE 16 Step 7F Clarified relay operation 11 16 2016 PAGE 17 Step 3I updated text PAGE 4 Updates to table and drawing Bracket and Spring C...

Page 24: ...Page 24 EI Manual Form No V3435EI 8 24 2017 U S Patents 6 402 944 6 444 127 6 776 901...

Reviews: