EI Man u al
Page 7
Con
fi
guration Settings
Step 1CS –
Press NEXT and
▼
simultaneously for 5 seconds and release. Press NEXT and
▼
simultaneously for 5 seconds and release. If the screen in Step 2CS does not appear, the lock on the valve is
activated. To unlock, press
▼
, NEXT,
▲
and REGEN in sequence, then press NEXT and
▼
simultaneously
for 5 seconds and release. Press NEXT and
▼
simultaneously for 5 seconds and release.
Step 2CS –
Use
▲
or
▼
to select 1.0 for 1” valve, 1.25 for 1.25” valve, 1.5 for 1.5” valve, 2.0 for 2” valve
or 1.0
for twin valve. If 1.0, 1.25 or 1.0
are selected, press NEXT to go to Step 4CS. If 1.5 or 2.0 are
selected, press NEXT to go to Step 3CS.. Press REGEN to exit Con
fi
guration Settings.
Step 1CS
Step 3CS –
Use
▲
or
▼
to select meter size. Settings available are 1.5,
2.0, 3.0, 1.0r (1.0 Remote Meter) or PUL (Variable Meter Calibration.)
Variable meter pulses of 0.1-150.0 PPL can be selected.
Press NEXT to go to Step 4CS. Press REGEN to return to previous step.
Step 2CS
Step 3CS
Step 4CS
Step 4CS –
Selecting the use of an outside signal to initiate a regeneration: Selection only matters if a
connection is made to the two pin connector labeled DP SWITCH located on the printed circuit board.
Following is an explanation of the options:
oFF - feature not used
NOTE: In a twin alternating system each control must have a separate dP signal or dP switch. One dP signal
or one dP switch cannot be used for both controls.
on0 – If the dP switch is closed for an accumulative time of 2 minutes a regeneration will be signaled to the
unit. In a twin alternating system the MAV will transition
fi
rst to switch units so that the signaled unit can
start regeneration. After the MAV has fully transitioned, the regeneration begins immediately. Note: For
WS1 – WS1.5 control valves programmed for twin alternating: if the dP function “on0” is set, the Delayed
Rinse and Fill feature is not available.
dEL – If the dP switch is closed for an accumulative time of 2 minutes a regeneration will occur at the
scheduled delayed regeneration time. In a twin alternating system once the dP switch is triggered the
PC Board will display “REGEN TODAY” and when the delayed regen time comes the control will
switch tanks and the triggered unit will then go into regeneration. Note: For WS1 – WS1.5 control valves
programmed for twin alternating: if the dP function “dEL” is set, the Delayed Rinse and Fill feature is not
available.
HoLd – If the dP switch is closed a regeneration will be prevented from occurring while there is switch
closure. In a twin alternating system the regeneration of a unit can be prevented upon switch closure. If the
unit depletes the capacity down to zero, it will not be allowed to switch tanks to regenerate until the switch
is open. Note: For WS1 – WS1.5 control valves programmed for twin alternating the Delayed Rinse and
Fill feature can be set.
Press NEXT to go to Step 5CS. Press REGEN to return to previous step.
Summary of Contents for Water Specialist EI
Page 1: ...Water Specialist EI Control Valve Programming and Cover Drawing Manual...
Page 2: ...Page 2 EI Manual...
Page 20: ...Page 20 EI Manual...
Page 21: ...EI Manual Page 21...
Page 22: ...Page 22 EI Manual...
Page 24: ...Page 24 EI Manual Form No V3435EI 8 24 2017 U S Patents 6 402 944 6 444 127 6 776 901...