Step 8F –
Set Relay Actuation Time or Liters using
▲
or
▼
. The choices are:
• Relay Actuation Time: After the start of a regeneration the amount of time that should pass prior
to activating the relay. The start of regeneration is de
fi
ned as the
fi
rst backwash cycle or brine cycle,
whichever comes
fi
rst. Ranges from 1 second to 200 minutes.
• Relay Actuation Liters: Relay activates after a set number of liters has passed through the meter. Ranges
from 1 to 200 liters.
Press NEXT to go to Step 9F. Press REGEN to return to previous step.
Step 8F
Step 9F –
Set Relay Deactivate Time using
▲
or
▼
.
• If Set Time on is selected in Step 7F the relay will deactivate after the time set has expired. Ranges from 1
second to 200 minutes.
• If Set Liters Filtering on or Set Liters Filtering Regen on is selected in Step 7F the relay will deactivate
after the time set has expired or after the meter stops registering
fl
ow, whichever comes
fi
rst. Ranges from 1
second to 20 minutes.
Press NEXT to exit OEM Filter System Setup. Press REGEN to return to previous step.
Step 9F
EXIT OEM FILTER SYSTEM SETUP
Step 7F –
Set Relay Operation using
▲
or
▼
. The choices are:
• Time on: Relay activates after a set time at the beginning of a
regeneration and then deactivates after a set period of time. The start of
regeneration is de
fi
ned as the
fi
rst backwash cycle or Dn brine cycle,
whichever comes
fi
rst.
• Liters Filtering on: Relay activates after a set number of liters have
been used while in service and then deactivates after the meter stops registering
fl
ow and the set time period
has expired.
• Liters Filtering Regen on: Relay activates after a set number of liters have been used while in service, or
during regeneration, and then deactivates after the meter stops registering
fl
ow and the set time period has
expired.
•ERROR: Relay closes whenever the valve enters error mode, and immediately deactivates when error
mode is exited. If set to ERROR, Steps 8F and 9F will not be shown.
• Off: If set to Off, Steps 8F and 9F will not be shown.
Press NEXT to go to Step 8F. Press REGEN to return to previous step.
Step 7F
Summary of Contents for Water Specialist EI
Page 1: ...Water Specialist EI Control Valve Programming and Cover Drawing Manual...
Page 2: ...Page 2 EI Manual...
Page 20: ...Page 20 EI Manual...
Page 21: ...EI Manual Page 21...
Page 22: ...Page 22 EI Manual...
Page 24: ...Page 24 EI Manual Form No V3435EI 8 24 2017 U S Patents 6 402 944 6 444 127 6 776 901...