90
SVGm
Instruction Manual
RS-485 Communications
Field bus
RS-485
Communications protocol
Modbus RTU
Baud rate
9600 bps
Stop bits
1
Parity
none
Ethernet communications
Network protocol
TCP/IP, Modbus TCP
User interface
Display
3.5” TFT colour touch screen
Web server and datalogger
Environmental features
Environmental conditions
Indoor conditioned IEC 60721-3-3
Operating temperature
-10ºC ... +45ºC
Storage temperature
-20ºC... +50ºC
Relative humidity (with no condensation)
0 ... 95%
Maximum altitude
3000 m a.s.l. ( 2000 m a.s.l. without performance degradation)
SVGm-3WF-xxxC-690, SVGm-4WF-xxxC-550
5000 m s.n.m.
Protection degree
IP20
Overvoltage category
OVC III 300V
SVGm-3WF-xxxC-690, SVGm-4WF-xxxC-550
OVC III 600V
SVGm-3WF-xxxC-480, SVGm-4WF-xxxC-400, SVGm-3WF-xxxC-690 and SVGm-4WF-xxxC-550
Pollution degree
2
Impact resistance
IK 10
Electromagnetic compatibility
Installation in type-A environments
Standards
Electromagnetic compatibility (CEM)� Part 6-4: Generic standards� Emissions stand-
ard for industrial environments� (IEC 61000-6-4:2006)�
UNE-EN 61000-6-4:2007
Industrial, scientific and medical equipment - Radio-frequency disturbance charac-
teristics - Limits and methods of measurement
UNE-EN 55011:2011
Electromagnetic compatibility (CEM)� Part 6-2: Generic standards� Immunity for in-
dustrial environments�
UNE-EN 61000-6-2:2006
Safety requirements for power electronic converter systems and equipment - Part 1:
General (Endorsed by AENOR in November of 2012�)
EN 62477-1:2012
Low-voltage switchgear and controlgear assemblies - Part 1: General rules
IEC 61439-1:2011
Summary of Contents for SVGm-3WF-100C-480
Page 1: ...SVGm M248B01 03 21A Static var generator INSTRUCTION MANUAL ...
Page 2: ...2 SVGm Instruction Manual ...
Page 98: ...98 SVGm Instruction Manual 14 CE CERTIFICATE ...
Page 99: ...99 Instruction Manual SVGm ...
Page 100: ...100 SVGm Instruction Manual ...
Page 101: ...101 Instruction Manual SVGm ...