62
SVGm
Instruction Manual
●
Invert
This parameter is used to select the phase whose filter is going to switch the current direction of the
load measurement transformer, so installation faults may be corrected.
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values.
7�7�- MEDIUM VOLTAGE
The reactive current in medium voltage can be compensated with the device
connected in low voltage
.
This requires using a low voltage to medium voltage step-up transformer, which can be one already
present in the installation or one used solely for this purpose.
, is used to set up the type of transformer and its transformation ratio.
Figure 65: Configuration screen: Medium voltage�
Activate the
Medium Voltage
option
so the device can compensate for reactive current.
●
Type Transf,
select the type of step-up transformer, as indicated on its rating plate.
●
Ratio,
select the transformation ratio.
Range of values:
High voltage:
66000 ... 1000 V
Low Voltage:
1000 ... 100 V
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values.
Summary of Contents for SVGm-3WF-100C-480
Page 1: ...SVGm M248B01 03 21A Static var generator INSTRUCTION MANUAL ...
Page 2: ...2 SVGm Instruction Manual ...
Page 98: ...98 SVGm Instruction Manual 14 CE CERTIFICATE ...
Page 99: ...99 Instruction Manual SVGm ...
Page 100: ...100 SVGm Instruction Manual ...
Page 101: ...101 Instruction Manual SVGm ...