7�4�- OPERATING LIMITS
Note:
This screen is not visible on the
“slave”
devices.
, the operating limits of the device are configured:
Figure 62: Configuration screen: Operating limits�
●
Min current
The minimum load current to start the static generator is configured with this parameter. Minimum
current feature is used to increase the system efficiency, by stopping the static generator when re-
quired. The
SVGm
will stop when the load current is below the entered value and will start when it is
higher.
Range of values:
Minimum value:
0 A
Maximum value:
5000 A
●
Current limit
This parameter allows the maximum power of the static generator to be limited. The value is config-
ured as a percentage with respect to the device’s rated power.
Range of values:
Minimum value:
20%
Maximum value:
100%
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values.