51
Instruction Manual
SVGm
Figure 49: Confirm screen�
This screen,
, shows the active warnings.
shows the warnings that can appear on the
device’s display.
Figure 50: Warnings�
Use the
and
keys to navigate through the different display screens.
Table 23: Warnings messages�
Warnings messages
Waiting for conditions
Description
The start-up conditions are not met.
Corrective
action
Check the alert messages.
Load polarity
Description
Detection of an error in the load polarity.
Corrective
action
Check the transformer connections. See section
“7.6.- TRANSFORMER CONFIGURATION”
Annual maintenance
Description
A year has passed since the last maintenance procedure was carried out and the maintenance meter
was reset.
Corrective
action
Perform the annual maintenance procedure and reset the maintenance meter. (see
)
Fan maintenance
Description
Fans have been operating for over 40,000 hours; they must be replaced and the maintenance meter
must be reset.