35
Instruction Manual
SVGm
3�8�- PARALLEL CONNECTION OF 2 TO 100 SVGm
The
SVGm
devices can be arranged in parallel.
Up to 100 devices can be arranged in parallel, either of
the
20�7
,
30, 41�4, 60, 67, 69
or
100 kvar
models.
In the case of installations with devices in parallel, a device must be defined as the “
master
”, while all
others will have “
slave
” devices functions.
The “
master
” will be responsible for measuring the network parameters, so only the current transform-
ers will be connected to it. This allows low-power transformers to be used in these installations, since
an individual transformer does not have to be connected to each device.
Master
1
2
100
...
Figure 28: Connection of 2 to 100 SVGm in parallel (Transformers on the mains side)�
Master
1
2
100
...
Figure 29: Connection of 2 to 100 SVGm in parallel (Transformers on the load side)�
New device can be connected to existing devices without having to shut down or disconnect them. This
ensures capacity can be increased or degraded device in critical installations can be replaced without
affecting the installation, allowing connection without shutting down the device and also making it
possible to achieve 0
MTD
(Maximum Tolerable Downtime).
In the event of failure of the “
master
” device, the front connection of the current transformers allows
connection to be changed to a “
slave
” device, reconfigured as the “
master
”, meaning the system re-
sumes operation quickly with minimum downtime.
Summary of Contents for SVGm-3WF-100C-480
Page 1: ...SVGm M248B01 03 21A Static var generator INSTRUCTION MANUAL ...
Page 2: ...2 SVGm Instruction Manual ...
Page 98: ...98 SVGm Instruction Manual 14 CE CERTIFICATE ...
Page 99: ...99 Instruction Manual SVGm ...
Page 100: ...100 SVGm Instruction Manual ...
Page 101: ...101 Instruction Manual SVGm ...