Press key
to display the different types of harmonics:
• Voltage harmonics L1- L2 - L3
• Current harmonics L1- L2 -L3
4�7�-
INPUTS
The
CVM-C10
has two digital inputs (terminals 12 and 13 on
and
) that can be
programmed to operate as a logic or tariff selection input.
If configured as a logic input, the device displays the status of that input.
See
“4.9.27. Operating mode of digital input 1”
“4.9.28. Operating mode of digital input 2”
The selected tariff can be determined in accordance with the status of the inputs, as shown in
Table 14: Selecting the tariff in accordance with the input status�
IN1, Input 1
IN2, Input 2
Tariff
Logic input
Tariff selection
Logic input
Tariff selection
x
x
T1
x
0
T1
x
1
T3
0
x
T1
1
x
T2
0
0
T1
0
1
T3
1
0
T2
1
1
T1
4�8�- OUTPUTS
The device features:
Two alarm relays (terminals 3, 4 and 5, as shown in
and
), fully pro-
grammable, see
“4.9.23. Programming alarm 1 (Relay 1)”
and
4.9.24. Programming alarm 2 (Relay
Two digital outputs, optoisolated NPN transistors (terminals 6, 7 and 8 on
and
), fully programmable, see
“4.9.25. Programming alarm 3 (Digital output T1)”
and
Programming alarm 4 (Digital output T2)”
Note:
The digital outputs are not available on models
CVM-C10-ITF-IN, CVM-C10-MC-IN
and
CVM-
C10-FLEX
45
Instruction Manual
CVM-C10