Table 23: Modbus memory map: Deleting parameters�
Parameters
Address
Valid data margin
Deleting energies
834
FF00
Deleting maximum and minimum values
838
FF00
Starting maximum demand
839
FF00
Deleting the hour counters (All tariffs)
83D
FF00
Deleting the maximum value of the maximum demand
83F
FF00
Deleting energies, maximum demand and maximum and min-
imum values
848
FF00
4�10�3�5� Power status�
All the Modbus map addresses are hexadecimal.
The
0x04 function
is implemented for this variable.
This variable indicates the quadrant in which the device is operating.
Table 24: Modbus memory map: Power status
Power status
Variable
Address
Default value
Power status
7D1
-
The variable format is shown in
Table 25: Variable format: Power status�
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
1:
Capacitive
1:
Inductive
1:
Generated
1:
Consumed
4�10�3�6� The unit’s serial number�
All the Modbus map addresses are hexadecimal.
The
0x04 function
is implemented for this variable.
Table 26: Modbus memory map: Serial number�
The unit’s serial number
Variable
Address
Default value
Serial number
578 - 579
-
4�10�3�7� Detection of incorrect direction of rotation
(Version 4.05 or higher)
All the Modbus map addresses are hexadecimal.
The
0x04 function
is implemented for this variable.
This variable indicates whether an incorrect direction of rotation has been detected in the voltages.
Table 27: Modbus memory map : Detection of incorrect direction of rotation�
Detection of incorrect direction of rotation
Variable
Address
Value
Detection of incorrect direction of rotation
7D5
0:
No fault has been detected
1:
Fault detected
78
CVM-C10
Instruction Manual