4�10�3�8�13� Programming alarms 3 and 4 (Digital outputs T1 and T2)
Note:
Configuration parameters not available for the
CVM-C10-FLEX , CVM-C10-ITF-IN and CVM-C10-
MC-IN
models
.
Table 40: Modbus memory map: Programming alarms 3 and 4�
Programming alarms 3 and 4
Configuration variable
Address
Valid data margin
Default
value
Relay 1
Relay 2
Kilowatts per impulse
2B0C-2B0D
2B16-2B17
0.001 - 999.999 kWh
0
Variable code
2B10
2B1A
0
Pulse width
2B11
2B1B
10 - 500
ms
100 ms
4�10�3�8�14� Digital inputs
Table 41: Modbus memory map: Configuration of digital inputs�
Configuration variable
Address
Valid data margin
Default
value
Input 1
Input 2
Operating mode
(11)
2B66
2B67
0
: Tariff
1
: Logic state
0
(11)
If Input 1 is configured as a tariff and Input 2 is configured as a logic state (or vice versa) we will only have 2 tariffs.
We can also read the status of the digital inputs when they are in logic mode:
The
0x04 function
is implemented for this variable.
Table 42: Modbus memory map: Status of the digital inputs (Logic state mode)
Status of digital inputs
Variable
Address
Default value
Status of digital inputs
4E20
-
The variable format is shown in
Table 43: Variable format: Status of digital inputs�
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
0
0
Input 2
0:
OFF
1:
ON
Input 1
0:
OFF
1:
ON
4�10�3�8�15� Digital outputs
Reading the status of the digital outputs.
The
0x04 function
is implemented for this variable.
Table 44: Modbus memory map: Status of the digital outputs
Status of the digital outputs
Variable
Address
Default value
Status of the digital outputs
4E21
-
The variable format is shown in
82
CVM-C10
Instruction Manual