Press key
for 3 seconds to edit the code selection. The
prog
icon will be displayed on the bottom
of the screen.
To enter or modify the value, press the
key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to
modify the other values.
When you enter the code of a variable on the display, the symbols for that variable will be activated.
Set the value to
00
if you do not wish to program a variable.
If you press the
key after changing the last digit, it will jump back to the first digit so you can
modify the previously programmed values again.
To validate the data, press
for 3 seconds and the
prog
icon will disappear from the display.
Press key
to access the next programming step
Table 18: Parameter codes used to program digital outputs�
Parameter
Tariff
Code
Tariff
Code
Tariff
Code
Tariff
Code
Consumed Active Energy
T1
49
T2
70
T3
91
total
112
Generated Active Energy
T1
59
T2
80
T3
101
total
122
Consumed Inductive Reactive
Energy
T1
51
T2
72
T3
93
total
114
Generated Inductive Reactive
Energy
T1
61
T2
82
T3
103
total
124
Consumed Capacitive Reactive
Energy
T1
53
T2
74
T3
95
total
116
Generated Capacitive Reactive
Energy
T1
63
T2
84
T3
105
total
126
Consumed Apparent Energy
T1
55
T2
76
T3
97
total
118
Generated Apparent Energy
T1
65
T2
86
T3
107
total
128
Consumed CO
2
Emissions
T1
56
T2
77
T3
98
total
119
Generated CO
2
Emissions
T1
66
T2
87
T3
108
total
129
Consumption Cost
T1
57
T2
78
T3
99
total
120
Generation Cost
T1
67
T2
88
T3
109
total
130
No. of hours
T1
68
T2
T3
110
total
131
If you have selected a parameter from
Table 12
the subsequent programming steps are the same as
for alarm relay 1, see (
“4.9.23. Programming alarm 1 (Relay 1)”
If you have selected a parameter from
the subsequent programming steps are:
64
CVM-C10
Instruction Manual