4�10�- COMMUNICATIONS
The
CVM-C10
devices have one RS-485 communications port.
The device has as standard two communications protocols:
MODBUS RTU
® and
BACnet
.
The protocol and configuration parameters are selected in the setup menu. (
Note:
BACnet protocol available in devices with version 3.00 or higher.
4�10�1� CONNECTIONS
The RS -485 cable must be wired with twisted pair cable with mesh shield (minimum 3 wires), with a
maximum distance between the
CVM-C10
and the master device of
1200 metres
.
A maximum of 32
CVM-C10
devices can be connected to this bus.
Use an intelligent RS-232 to RS-485 network protocol converter to establish the communications with
the master device.