106
Po/Pn(%)
100%
80%
60%
40%
20%
0
0.88Un 1.0Un 1.1Un
Figure 8-3
CPS SCH100/125KTL-US-600 and SCH100KTL-US-480 Derating Curve of
Grid Voltage
When the grid Voltage is within 100%
~110% of the rated output voltage, the
inverter output power may reach 100%. When the grid voltage is lower than
100%, the inverter will limit the AC Output Current and the output power will
begin to derate, as shown in Figure 8-3.