104
20%
40%
60%
80%
100%
PV Voltage (V)
Po/Pn
(
%
)
860 900 1300 1450
0
Figure 8-1
CPS SCH100/125KTL-US-600 derating curve of PV input voltage
Figure 8-2
CPS SCH100KTL-US-480 derating curve of PV input voltage
When the DC input voltage is higher than 1300V, the inverter begins derating,
as shown in Figures 8-1 and 8-2
.
20%
40%
60%
80%
100%
PV Voltage (V)
Po/Pn
(
%
)
750 900 1300 1450
0