46
CPS SCH100KTL-DO/US-600, SCH125KTL-DO/US-600
and SCH100KTL-
DO/US-480 inverters support industry standard SunSpec and Modbus RS485
communication. Below is a description of the components of the
communication card and its location in the inverter wire-boxes.
Communication board description
Figure 3-29 Communication Board
4
1
2
3
5
①
RS485 (Reserved)
②
Power port (2pin connector)
1.
GND
2.
+12V
③
RS485 port (6pin connector)
1.
485_A
2.
485_B
3.
485_GND
4.
485_A
5.
485_B
6.
485_GND
④
Selector Switch (S201): 120Ω
terminal resistor switch for
communications.
1.
ON: Enable the
termination resistance
2.
OFF: Disable termination
resistance
⑤
RJ45(Reserved)