3.3.4 DC Connection
DC fuse configuration
CPS SCH100/125KTL-US-600 and SCH100KTL-DO/US-480 inverters are
equipped
with 20A DC fuses. Customers must verify that the appropriate fuses
are installed depending on the actual configuration of PV strings.
1)
Each DC input from the PV strings requires fuse protection.
2)
The rated voltage of the fuse should be 1500Vdc.
3)
The rated current of the fuse is generally 1.56 × short circuit current
from the PV strings, rounded to the next available fuse size.
NEC2017 alternate calculation method may yield a smaller fuse.
The following table lists the fuse type, specifications and number under the
rated voltage and power range of 20 strings of PV panels.
Table 3-12 DC Fuse selection
Note 1: The 1500VDC ADLER fuse series are recommended.
Detailed information is available for customers to find and
download from
http://www.adlerelectric.com/.
WARNING: Use of different fuses or incorrectly sized fuses
can cause damage to equipment or create unsafe working
conditions. Any damage resulting from incompatible fuses
is not covered by warranty.
100-125
kW
Brand
15A/1500V
20A/1500V
ADLER
A742150b00
A742200b00
SINOFUSE
RS308-PV-5F15A
RS308-PV-5F20A