27
6 %
TEST
Before the measurement: to display the measurements already recorded.
During or after the measurement: to record it.
The direction of the arrow indicates whether you can make a reading (arrow pointing out) or a recording (arrow
pointing in).
The percentage indicates the quantity of memory already used.
Press the TEST button to start the measurement. The measurement stops automatically.
When the TEST key is pressed, the device checks that the contact voltage is less than U
L
. If not, it does not make
the loop impedance measurement.
This symbol invites you to wait while the measurement is in progress.
To activate or deactivate the smoothing of the signal.
050.00
k
Ω
Ω
(Ik)
To compensate for the resistance of the measurement leads, for measurements of low values (see §3.14).
To deactivate the alarm.
To activate the alarm on Zi.
To set the alarm threshold (see §3.15). As default,
the threshold is set to 50
W
.
Before starting the measurement, you can configure it by modifying the parameters displayed:
Z-R
Ik
010.00
A
k A
To activate the alarm on Ik.
To set the alarm threshold (see §3.15). As default,
the threshold is set to 10 kA.
The device proposes choosing the voltage for the Ik calculation from among the following values:
U
LN
(the measured voltage value),
the voltage of the old standard (for example 220 V),
the voltage of the current standard (for example 230 V).
Depending on the voltage U
LN
measured, the device proposes the following choices:
if 170<U
LN
<270 V: U
LN
, 220 V, or 230 V.
if 90<U
LN
<150 V: U
LN
, 110 V or 127 V.
if 300<U
LN
<500 V: U
LN
, 380 V or 400 V.