49
POWER
03
/
03
/
2009 10
:
47
50 . 1 Hz
12 %
+ 6 4 W
U 2 3 2 . 5 V
I 2 7 8 . 1 mA
PF + 0 . 8 7
3.12.3. READInG of tHE REsUlt
Measurement result.
The + sign indicates power con-
sumed. The - sign indicates power
returned.
Voltage between the L and PE ter-
minals.
Current measured by the clamp.
Power factor.
The + sign indicates that the load
is resistive or inductive. The - sign
indicates that the load is capacitive.
The clamp is connected.
If the phase of the current with respect to the voltage is not correct, turn the clamp around, with the help of the arrow marked on
the jaws, in order to reverse the phase by 180°.
POWER
03
/
03
/
2009 10
:
47
50 . 1 Hz
U
RMS
= 232.5 V
U
MAX
= 328.8 V
I
RMS
= 278.1 mA
I
MAX
= 393.3
mA
Numerical values.
Voltage curve.
Current curve (thicker line).
Press this function key to display the voltage and current curves, as on an oscilloscope. If the clamp is not con-
nected, only the voltage curve is displayed. The current curve cannot be displayed alone.
The representation of the curves is normalized:
in amplitude, the curves are automatically adjusted to fill the screen.
on the time scale, approximately one period is shown.
To move the text if it masks part of the curves.
Summary of Contents for C.A 6116
Page 1: ...C A6116 Installation TESTER E N G L I S H User s manual...
Page 95: ...95...