REVO C
1PH from 300A to 800A
User’s manual
71
14.2 Current Limit tuning procedure
• Give the power supply and set the current limit to zero:
- In analog mode, set the analog input 2 to zero
- In digital mode, set the parameter=0
• Start the thyristor unit.
• Set the primary input or the setpoint value at 100%
• Increase the current limit
- In analog mode increase the value of the analaog input
- In digital mode increase the parameter until to reach the desired value of rms current.
• Stop the thyristor unit.
The Current Limit Procedure is done.
Use the configurator software to set the desired current limit value.