42
REVO C
1PH from 300A to 800A
User’s manual
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Alm Out Fn
Choose for which conditions the digital output
indicates alarm. The output always indicate an
alarm when the heat sink is over temperature. The
digital output is energized for normal operating
condition and de-energized when the power
controller is off or when there is an alarm.
Note!:
The power controller monitors for heater
break or short circuit condition only when included
in the option selected for Alarm Output Function
1
34
Read
Write
Option
Description
Bit
Heater Break
Heater Break
0
Short Circuit
Short circuit
1
Current Limit
Current Limit
2
Therm
SCR is over temperature
3
Communication
Communication watchdog error
4
DEFAULT
None
Alarm Bitwise is allowed
Parameter Name
Description
Default
Modbus
Address
Par.
Type
IL SP Src
Choose how the current limit is set
16
14,bit 4
Read
Write
Option
Description
Value
Local / Comms
Set point set via keypad or communication
16
Analog In 2
Set point set via analog input
0
DEFAULT:
local
16
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Retransmit
Choose which parameter is retransmitted by the
analog output
12
68
Read
Write
Option
Description
Value
Set Point
Set point
0
Volts Out
RMS voltage output
15
Power
Average output power
10
Current
RMS current output
11
None
Do not retransmit value
12
DEFAULT:
Power
12