18
REVO C
1PH from 300A to 800A
User’s manual
Technical Specifications
6.1 General features
Cover and Socket material:
PolymericV2
Utilization Category:
AC-51 AC-55b AC-56A
IP Code:
20
Method of Connecting:
Single Phase load
Auxiliary voltage:
Order code RC1_ _ _ -_1 = line voltage 100/120V transformer range 90:135V (8 VA Max)
Order code RC1_ _ _ -_2 = line voltage 200/208/220/230/240V transformer range 180:265V (8 VA Max)
Order code RC1_ _ _ -_3 = line voltage 277 transformer range 238:330V (8 VA Max)
Order code RC1_ _ _ -_5 = line voltage 380/400/415/440/480V transformer range 342:528V (8 VA Max)
Order code RC1_ _ _ -_6 = line voltage 600V transformer range 540:759V (8 VA Max)
Order code RC1_ _ _ -_7 = line voltage 690V transformer range 540:759V (8 VA Max)
Relay output for Heater Break Alarm:
0.5A a 125VAC
(only with HB option)
6.2 Input features
Digital Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc) 0,5Hz max
Volt Analogic input:
0 ÷ 10Vdc impedance 15 kΩ
Current Analogic input:
0 ÷ 20mA impedance 100 Ω
4 ÷ 20mA impedance 100 Ω
Potentiometer:
10 kΩ min.
Logic input SSR (Fast Enable):
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc)
duty cycle min. 100 ms max 3Hz
6.3 Output features (power device)
Current
Nominal
Voltage
range (Ue)
Repetitive peak
reverse voltage
(Uimp)
Latching
current
Max peak
one cycle
Leakage
current
FUSE I2T
value
Suggested
A2s
(at500V)
Frequency
range
Power loss
Thy
Fuse
Isolation
Voltage
(Ui)
(A)
(V)
(480V)
(600V)
(mAeff)
(10 msec.)
(A)
(mAeff)
tp=
10msec
(Hz)
I =Inom (W)
(Vac)
300
24÷600
1200
1600
200
7800
15
73500
47÷70
443
3000
400
24÷600
1200
1600
200
7800
15
150500
47÷70
547
3000
500
24÷600
1200
1600
1000
17800
15
294000
47÷70
591
2500
600
24÷600
1200
1600
1000
17800
15
246400
47÷70
832
2500
700
24÷600
1200
1600
1000
17800
15
246400
47÷70
945
2500
800
24÷600
1200
1600
1000
15000
15
246400
47÷70
1144
2500
6
Summary of Contents for REVO C