28
REVO C
1PH from 300A to 800A
User’s manual
NOTE:
1
The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator.
The Fuse must be branch circuit protection. For UL any listed UL branch circuit fuse would be acceptable
as an external fuse, following national electric code guide for resistive heating of 125% load current rating
to protect external wires.
2
The auxiliary voltage supply of the REVO C unit must be synchronized with load voltage power supply. If
the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load), use
an external transformer as designated.
3
For SSR input connection follow next page schematic.
4
IMPORTANT! Starting Strategy (Enable)
:
1: Feed the unit with L1-L2-L3 power voltage supply
2: Feed the auxiliary supply
3: Close the Enable contact to start with the regulation
MICRO
USB 2.0
M2
M1
M1
9
18
15 16
20
10 13
12 11
10
10
11
4
3 1 2
8
7
A+
B-
5
6
M5
4
+
-
Ethernet
Profibus
RETRANS. OUT
3
4
24Vdc input
+24V
GND
L2/N L1
Option
Second
Serial RS485
Fuse
5A Max
Branch Circuit
Protection
Analog Inp.1
Analog SetPoint
Analog Inp.2
Reference
Ext.FeeDBack
Ext.Current Limit
Analog Input 2
Analog Input 1
Fan Supply
230Vac Standard
115Vac Option
24Vdc Option
See Order Code
Function
Thermal
SC/HB/CL
TO LOAD
Caution:
this procedure must be performed only by qualified persons.