Appendix A: TV-VVTZC-E2 Points/Properties
TruVu™ VVTZC
-E2
©2022 Carrier.
Installation and Start-up Guide
All rights reserved.
117
Point Name/Description
Default/Range
Reheat Min Damper Position
–
For Single Duct units with ducted reheat. Set to
the desired damper position at which the reheat will provide optimum
performance. This value is compared to the
Cooling Min Damper Position
value,
and the greater of the two values determines the damper position.
D:
R:
45%
0 to 100%
Heating Min Damper Position
–
The minimum damper position the terminal
controls to when the air source mode is Heat and the space requirements are at a
minimum.
D:
R:
20%
0 to 100%
Heating Max Damper Position
–
The maximum damper position the terminal
controls to when the air source mode is Heat and the space requirements are at a
maximum.
D:
R:
20%
0 to 100%
Vent Position
–
The ventilation damper position the terminal controls to when the
air source mode is Vent and the terminal mode is not in the Heat or Cool mode. If
Linkage is not active, the zone determines vent mode by verifying that its SAT
sensor is between 65°F (18.3°C) and 80°F (26.6°C).
D:
R:
50%
0 to 100%
Test and Balance
–
Use the following command buttons when commissioning a zone,
balancing the system
(page
55), replacing the zone controller, or troubleshooting. If
Automatic Control
is not selected within 4 hours, the
controller will resume normal control.
Calibrated Damper Close
–
Forces the damper closed so the 0% damper position can be set.
Calibrated Damper Open
–
Forces the damper to its maximum open position so that the 100% damper position can
be set.
Cool Max
–
Forces the damper to its cool maximum position regardless of its current local mode.
Cool Min
–
Forces the damper to its cool minimum position regardless of its current local mode.
Automatic Control
–
Returns the damper to its normal control routines.
This must be activated when you finish
using any of the other Test and Balance commands.
Damper Full Close
–
Overrides the damper to its full closed position.
Heat Max
–
Forces the damper to its heat maximum position regardless of its current local mode.
Heat Min
–
Forces the damper to its heat minimum position regardless of its current local mode.
Reheat Min
–
Forces the damper to its reheat position regardless of its current local position.
Vent
–
Forces the damper to its ventilation position regardless of its current local mode.
Sensor Binder / Zone Temp / Zone Humidity / ZS Zone CO2
Ctrl+click
on the name of these properties to access the microblock popup
Properties
page >
Details
tab. See below for instructions on configuring your ZS or wireless sensors.
See the microblock Help for more detailed explanations.