Appendix A: TV-VVTZC-E2 Points/Properties
TruVu™ VVTZC
-E2
©2022 Carrier.
Installation and Start-up Guide
All rights reserved.
121
Maintenance
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Maintenance
Point Name/Description
Default/Range
Unit
Occupancy Status
–
The controller's occupancy status as determined by a network
schedule, a local schedule, or a timed override.
R: Unoccupied/Occupied
Temp Compensated Start
or
Learning Adaptive Start
–
Indicates the type of optimal
start (if any) that is configured and whether the algorithm is active or inactive.
R: Inactive/Active
Space Temp Source
–
The source of the controlling space temperature value.
Options:
Sensor Failure
–
No valid space temperature or sensor status = failed.
SPT Sensor
–
An SPT sensor is connected to the controller's Rnet port.
T55/56
–
A T55, T56, or T59 sensor is connected to the controller's I/O terminals.
Network
–
A network temperature sensor is bound to the controller's space
temperature AV.
Airside Linkage
–
The space temperature from a linked terminal.
Locked Value
–
The controller's space temperature input has been manually locked at a
value.
ZS Sensor
–
A ZS sensor is connected to the controller's Rnet port.
R: Sensor Failure
SPT Sensor
T55/T56
Network
Airside Linkage
Locked Value
ZS Sensor
Setpoint Adjustment
–
The amount that a user has adjusted the setpoints on a zone
sensor.
R: -20 to 20 °F
(-11.1 to 11.1 °C)
Effective Heat Setpoint
–
The current heating setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from
Optimal Start
to
Demand
Limit
.
R: _°F/C
Effective Cool Setpoint
–
The current cooling setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from
Optimal Start
to
Demand
Limit
.
R: _°F/C
Relative Humidity Source
–
The source of the relative humidity value.
R: N/A
Local
Network
Linkage
Locked Value
ZS Sensor
IAQ Source
–
The source of the indoor air quality value.
R: N/A
Local
Network
Linkage
Locked Value
ZS Sensor
Outdoor Air Temperature Source
–
The source of the outdoor air temperature.
R: N/A
Local
Network
Linkage
Locked Value
Cooling Demand Level
–
The system cool demand level received over the network.
R: 0 to 3