What is the TV-VVTZC-E2?
TruVu™ VVTZC
-E2
©2022 Carrier.
Installation and Start-up Guide
All rights reserved.
4
The TV-VVTZC-E2 also has the following ports:
•
Rnet port for connecting ZS sensors, an Equipment Touch, an TruVu™ ET Display, and Wireless Adapter for
wireless sensors
•
Comm/Service USB ports for connecting locally to controller set
up pages, the TruVu™ ET Display, or the
Carrier wireless service adapter
•
Act Net port supports a combination of up to 5 Act Net addresses. Act Net devices must be addressed as
follows:
○
Address
1
is reserved
for the built-in actuator
○
Address
2
and
3
are reserved for the VAV Zone II Secondary Duct
○
Address
4
and
5
for i-Vu® Smart Valves
Specifications
Driver
drv_fwex_< version >.driverx
Maximum number of control programs
NOTE
Programs may be limited by hardware.
2
NOTE
You can run 1 VVT zone Product Integrated Control
(PIC) and 1 programmable Zone Controller II program, OR
up to 2 Zone Controller II programs.
Maximum number of BACnet objects*
12000
Third-party BACnet integration points
NOTE
Must be on the BACnet/IP network.
100
* Depends on available memory.
Power
24 Vac ±15%, 50
–
60 Hz, 50 VA
24 Vdc ±10%, 18 W
NOTE
The above power consumption is for the controller only. Adding devices to
the Act Net bus increases total power consumed.
Actuator
Belimo brushless DC motor, torque 45 inch-pounds (5 Nm), runtime 154 seconds
Eth0, Eth1
10/100 BaseT, full duplex, Ethernet ports for BACnet/IP and/or BACnet/Ethernet
communication.
Under normal operation, network traffic not destined for this controller is repeated
to the other Ethernet port. When the controller is powered off, all traffic received on
one port is mirrored to the other port.