Appendix A: TV-VVTZC-E2 Points/Properties
TruVu™ VVTZC
-E2
©2022 Carrier.
Installation and Start-up Guide
All rights reserved.
123
Local BACnet Schedule
R: Off/On
Configure ZS Sensors by setting the following options in the
Local BACnet Schedule
microblock popup. Click
Local BACnet Schedule
to access the microblock popup
Properties
page >
Details
tab.
See the microblock Help for more detailed explanations.
Sensor Configuration
Allow Force Unoccupied:
–
Check to allow a user to save energy by
forcing the zone into an unoccupied schedule on the ZS sensor. The
user does this by holding the sensor's On/Off button for at least 3
seconds. This forced state remains in effect until the schedule
transitions to unoccupied or until a user presses the sensor's On/Off
button again.
D:
R:
Enabled
Disabled/Enabled
Force Unoccupied without Delay:
–
Check to allow a user to force a zone
to unoccupied immediately instead of the normal 3-second delay.
NOTE
This option is not available if
Allow TLO Set During Occupied
is
checked.
D:
R:
Enabled
Disabled/Enabled
Timed Local Override
Increment:
–
Minutes that the microblock adds to the zone's occupied
time for each click of the zone's local override button or switch.
D: 30:00 mm:ss
Maximum Duration:
–
Maximum value (up to 960 minutes) the
microblock outputs, regardless of additional pulses from the controller's
input.
D:
R:
60:00 mm:ss
0 to 960:00 mm:ss
Environmental Index
Environmental Index (EI)
–
Initial
Occupied
value is 100%. A value of 0% means the zone
is
Unoccupied
. If the space temperature deviates from
Effective Heat Setpoint
and
Effective Cool Setpoint
range, the value is derated. EI supports an optional RH and/or
CO
2
sensor. The RH and/or CO
2
values could also derate an EI.
R:
0 to 100%
EI Time Satisfied
–
Percentage of
Occupied
time during which a zone maintains an EI of
70% or higher.
R:
0 to 100%
Weighted EI
–
Determines the priority of a zone in an EI roll-up, which must be
completed using a different control program.
R:
0 to 100000.0
EI Total Weight
–
Current
EI Weighting Factor
used to scale the
Weighted EI
.
R:
0 to 1000.0
EI Decreased By
–
Source(s) of an EI value reduction.
Options:
Temp
–
EI decreased by Space Temperature
Temp & RH
–
EI decreased by Space Temperature and Relative Humidity
Temp, RH, & CO2
–
EI decreased by Space Temperature, Relative Humidity, and CO2
RH
–
EI decreased by Relative Humidity
RH & CO2
–
EI decreased by Relative Humidity and CO2
CO2
–
EI decreased by CO2
Temp & CO2
–
EI decreased by Space Temperature and CO2
None
–
No source(s) decreasing Environmental Index value
R:
Temp
Temp & RH
Temp, RH, & CO2
RH
RH & CO2
CO2
Temp & CO2
None