44
Fig 20
– Soleplate dimensions
3.4.3 Installation of spring isolation system
Spring isolation may be purchased as an accessory from Carrier for field installation. It may also be field supplied
and installed. Spring isolators may be placed directly under machine support plates or located under machine
soleplates. See Fig. 21. Low profile spring isolation assemblies can be field supplied to keep the machine at a
convenient working height.
Obtain specific details on spring mounting and machine weight distribution from job data. Also, check job data for
methods to support and isolate pipes that are attached to spring isolated machines.
NOTE: The springs are designed to support the weight of the chiller only. Connected piping must be supported
independently of the chiller.
NOTE: It is recommended that any installation other than the ground floor should have spring isolation for the
chiller and piping.
NOTE: These isolators are not intended for seismic duty, but are intended to reduce the vibration and noise levels
transmitted from the chiller to the surrounding environment. For installations adjacent to areas that are sensitive to
noise and/or vibration, use the services of a qualified consulting engineer or acoustics expert to determine whether
these springs will provide adequate noise/vibration suppression.
Summary of Contents for PIC 5+
Page 26: ...26 VFD not shown Fig 13 Sensors actuators location ...
Page 52: ...52 Fig 24 19DV control box ...
Page 53: ...53 1 Power supply 24V AC 2 LEN 3 CCN 4 Ethernet 5 USB Fig 25 19DV HMI box rear view ...
Page 54: ...54 Fig 26 19DV IOB1 wiring Fig 27 19DV IOB2 wiring ...
Page 57: ...57 ...
Page 113: ...113 APPENDIX A SmartView SCREEN AND MENU STRUCTURE ...
Page 114: ...114 Detailed menu description ...
Page 116: ...116 APPENDIX B MAINTENANCE SUMMARY AND LOGSHEETS Cont 19DV monthly Maintenance Log ...