![Carrier PIC 5+ Installation, Operation And Maintenance Instructions Download Page 110](http://html.mh-extra.com/html/carrier/pic-5/pic-5_installation-operation-and-maintenance-instructions_2562218110.webp)
110
10.6 Check Sensor Accuracy
Place the sensor in a medium of known temperature and compare that temperature to the measured reading. The
thermometer used to determine the temperature of the medium should be of laboratory quality with 0.25 °C
graduations. The sensor in question should be accurate to within 1.2 °C.
Note that the PIC5+ control module, MAINTENANCE menu, offers a temperature sensor calibration feature where
the sensor temperature can be offset. Note that only the four water temperatures can be calibrated. To use this
feature, place the sensor @ 0°C or other known temperature. Read the raw temperature and calculate offset
based on the reading seen in the TEMP_CAL menu. Enter and execute the offset, which cannot exceed ± 1.2°C.
The sensors are immersed directly in the refrigerant or water circuits. When installing a new sensor, apply a pipe
sealant or thread sealant to the sensor threads.
An additional thermistor, factory installed in the bottom of the cooler barrel, is displayed as Evap Refrig Liquid
Temp on the TEMPERATURES display screen. This thermistor provides additional protection against a loss of
water flow.
DUAL TEMPERATURE SENSORS
For servicing convenience, there are 2 redundant sensors each on the bearing and motor temperature sensors. If
one of the sensors is damaged, the other can be used by simply moving a wire. The number 2 terminal in the
sensor terminal box is the common line. To use the second sensor, move the wire from the number 1 position to
the number 3 position. See fig 59 and 60.
Fig 59
– 1
st
stage / 2
nd
stage Bearing Temperature (RT39C / RT40C) sensor wiring
Fig 60
– Winding Temperature (RT31C) sensor wiring
Summary of Contents for PIC 5+
Page 26: ...26 VFD not shown Fig 13 Sensors actuators location ...
Page 52: ...52 Fig 24 19DV control box ...
Page 53: ...53 1 Power supply 24V AC 2 LEN 3 CCN 4 Ethernet 5 USB Fig 25 19DV HMI box rear view ...
Page 54: ...54 Fig 26 19DV IOB1 wiring Fig 27 19DV IOB2 wiring ...
Page 57: ...57 ...
Page 113: ...113 APPENDIX A SmartView SCREEN AND MENU STRUCTURE ...
Page 114: ...114 Detailed menu description ...
Page 116: ...116 APPENDIX B MAINTENANCE SUMMARY AND LOGSHEETS Cont 19DV monthly Maintenance Log ...